Permit Number: T22CM01167
Parcel: Unknown

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM01167
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Secure the refrigerant circuit access ports of the condensing units to prevent unauthorized access. Reference: Section 1101.10, IMC 2018.
02/24/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the gas diagram on sheet P2.0 to show the size of the gas main between AHU-9 and AHU-10. Reference: Section 402.2, IFGC 2018.
03/15/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Verify there are adeqate maintenance receptacles throughout the building to provide for HVAC equipment maintenance power. NEC 210.63

2. The printing in the electrical plans at the bottom of the plan sheets and OCPD rating in the panel schedules is not legible. Please correct the issue and resubmit the plans.

Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements

Final Status

Task End Date Reviewer's Name Type of Review Description
03/15/2022 NGARCIA3 OUT TO CUSTOMER Completed