Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T22CM01162
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM01162
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/23/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the new HVAC unit. Reference: Section C403.1.1 and C403.3.1, IECC 2018.
2. Show that the proposed new HVAC equipment meets the minimum performance requirements of Section C403.3.2, IECC 2018.
02/23/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide drinking fountains per Table 403.1 and Section 410.3, IPC 2018 (see also the Code Review Checklist on sheet A1.0).
2. Verify the size of the existing natural gas main. Based on Table 402.4 (2), IFGC 2018, a ¾" pipe can only accommodate 104 MBH at 100 feet of developed length. Reference: Section 402.3, IFGC 2018.
02/23/2022 ROBERT SHERRY WATER REVIEW Completed
03/05/2022 JVINCEN1 FIRE REVIEW Approved
03/10/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/14/2022 SSHIELD1 ENGINEERING REVIEW Passed
03/14/2022 STEVE SHIELDS ZONING REVIEW Approved
03/14/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed