Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM01161
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/23/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G1; Code Check: The Occupancy Group is listed as R-1. The IBC Section 310.2 indicates an R-1 as boarding houses or congregate living facilities with more than 10 occupants. Revise the Occupancy Group to R-3 per the IBC Section 310.4 (care facility) with 5 or fewer persons. 2. Sheet G1; Code Check: The Occupant Load is calculated as 9 occupants. The maximum Occupant Load per the IBC Section 310.4 is 5 for an R-3 Occupancy Classification. Please revise. 3. Sheet G1; General Building Summary: Under "Sprinkler System" in this table, "No" is indicated. Please revise. 4. General: Please provide a project valuation (labor + materials). 5. General: Please provide written responses to all review comments. |
| 02/23/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the new HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018. 2. Show that the proposed new HVAC equipment meets the minimum performance requirements of Section C403.3.2, IECC 2018. |
| 02/23/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | If the shower does not have a prefabricated receptor, provide details to show that the construction of the receptor complies with the requirements of Section 421.5, IPC 2018. |
| 02/23/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/09/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. Show the locations and power source for the Ductless Heat Pumps and correlate with the panel schedules. Update load calculations as necessary. See Mechanical plans for additional information. 2. Exhaust fan light and Heat combo #1 requires 14 amps and timeclock controls per Mechanical plans. Please indicate this on the power and or lighting plans. See Mechanical plans for specifications. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |
| 03/15/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 03/15/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/05/2022 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 04/29/2022 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.) Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp. Instructions: 1. Is this for a new or existing activity application? - Please select New Application. 2. Submission Type - Select Floodplain Use Permit. 3. Project Name - Enter a name for your project. 4. Type of Permit - Select Commercial or Residential (Residential is for work on single family residences and duplexes.) 5. Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided. 6. Description of Work - Enter in Floodplain Use Permit for…and then put a description of the work being done or reference the building permit number associated with this floodplain use permit. 7. Complete the Applicant Info. (Note APA# is for applicants with an advance payment account. Leave blank is you do not have an APA account. 8. Complete the Contractor, Owner and Architect/Engineer sections as applicable. 9. Supporting Documentation Upload - Provide a complete cost estimate for the project unless it is for a new build/separate structure. You may also provide additional documents you think will be helpful. 10. Sign the application and submit. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |