Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM01141

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. The occupant load is calculated incorrectly both unconcentrated and fixed seating is present. Please review Sections 1004.5 and 1004.6 on how to calculate both types of seating. Section 1004.6 specifically provides direction on calculating fixed seating. Provide the calculations used to determine the occupant load.


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Approved

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
04/03/2022 JVINCEN1 FIRE REVIEW Reqs Change See building comments:

Denied
1. The occupant load is calculated incorrectly both unconcentrated and fixed seating is present. Please review Sections 1004.5 and 1004.6 on how to calculate both types of seating. Section 1004.6 specifically provides direction on calculating fixed seating. Provide the calculations used to determine the occupant load.