Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2022 SBLOOD1 ENGINEERING REVIEW Passed
03/02/2022 PAUL CAMARENA ZONING REVIEW Approved
03/08/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T22CM01135
PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
GENERAL REQUIREMENTS:
The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.
Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits
GENERAL COMMENTS:
1. Items built without permit may require alteration or improvement for achieving code compliance with the 2018 IRC, R105. Complete construction plans are required for processing a building permit. The plans should show necessary structural changes for achieving building code compliance, 2018 IRC.

SITE PLAN:
1. Indicate the location of buildings and any utilities supporting or effecting the proposed structure.

FOUNDATION PLAN:
1. Dimension the footing length, width, and depth into undisturbed soil for each footing type and condition, R403.1. Show the minimum 12” reinforced footing depth below the undisturbed ground surface R403.1. Show rebar reinforcement with 3” clearance from earth, R403.1.3.5.3. Provide ½” anchor bolts with 7” embedment, R403.1.6.


SECTIONS - DETAILS:
1. Show the Post Section Detail with #4 rebar in the footing, R403.1.
2. Notate and specify pressure treated sills in contact with concrete.
3. Show ledger fastener size and spacing.
Please contact the plans reviewer if you have any questions:
Ken Van Karsen
520 837-4912
City of Tucson Residential Plan Review
03/23/2022 IMONSHI1 NPPO REVIEW Passed