Permit Number: T22CM01102
Parcel: 136336000

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T22CM01102
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2022 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T22CM01102
Residential Addition
March 07, 2022

The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed.

1. There appears to be an unpermitted, attached addition on the east side of the house. The addition does not appear on the plans. If the addition is no longer present, please make a note indicating that on the site plan. If it is there, and is to remain, it will need to be permitted. A DDO or variance may be necessary to reduce the setbacks, depending on the placement. More information is required.
2. The small detached structure in the back yard does not appear on the site plan. If it is still present, please add it on the next submittal.

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp. If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov
03/08/2022 KKARSEN1 FIRE REVIEW Passed
03/08/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Show rebar reinforcement for CMU at Detail #1. Show R-13 wall insulation at 2x4 cavities.

R-30 batt insulation completely fills a 2x8 cavity. Remove the eave vent holes and notation.

An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/08/2022 NGARCIA3 OUT TO CUSTOMER Completed