Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM01095
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM01095
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2022 SBLOOD1 ENGINEERING REVIEW Passed
02/22/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/23/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide general room exhaust for any cooking appliance that does not require the installation of a Type II hood (e.g. waffle bakers). The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 2 and 507.3, IMC 2018.
02/23/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/23/2022 ROBERT SHERRY WATER REVIEW Completed
03/05/2022 JVINCEN1 FIRE REVIEW Approved
03/09/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/14/2022 STEVE SHIELDS ZONING REVIEW Approved
03/14/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed