02/14/2022 AHOLLIS1 OIP REVIEW Reqs Change FROM: Alex Hollis
PDSD Residential Review Section

PROJECT: T22CM01091



TRANSMITTAL DATE: February 14, 2022



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments

COMMENT: Based on the developed length of 42 ft, the half inch pipe to the furnace is undersized. The half inch will only supply 72,000 BTU and the wall furnace needs 75,000 BTU.

COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Alex Hollis any time during the week by email alex.hollis@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans