Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM01091
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/14/2022 | AHOLLIS1 | OIP | REVIEW | Reqs Change | FROM: Alex Hollis PDSD Residential Review Section PROJECT: T22CM01091 TRANSMITTAL DATE: February 14, 2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed. COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments COMMENT: Based on the developed length of 42 ft, the half inch pipe to the furnace is undersized. The half inch will only supply 72,000 BTU and the wall furnace needs 75,000 BTU. COMMENT: Residential will review the application on the next submittal If you have any questions about this transmittal, Contact Alex Hollis any time during the week by email alex.hollis@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/14/2022 | VVERA1 | OUT TO CUSTOMER | Completed |