Permit Number: T22CM00953
Parcel: 115052410

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM00953
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2022 SBLOOD1 ENGINEERING REVIEW Passed
02/17/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/17/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance of the replacement windows with the current code. Reference: Section R503.1.1.1, IECC 2018.
2. Provide instructions for setting the operating parameters of the new smart exhaust fan to provide whole-house ventilation. Reference: Section R403.6, IECC 2018.
02/17/2022 ROBERT SHERRY WATER REVIEW Passed
02/18/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/18/2022 JVINCEN1 FIRE REVIEW Approved
03/07/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Provide complete up to date electrical plans that correlate with the Mechanical and Plumbing plans installation. Correlate equipment specification requirements for voltage, amperage, phase, and maintenance receptacles (where required per NEC) between Electrical and Mechanical/Plumbing plans. Include electrical load calculations where load increases from the original installation.

2. All Electrical plans are required to be sealed by a Registrant registered in the State of Arizona.

Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
03/08/2022 IMONSHI1 ZONING REVIEW Approved
03/08/2022 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed