Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM00953
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/16/2022 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
02/17/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
02/17/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Demonstrate energy code compliance of the replacement windows with the current code. Reference: Section R503.1.1.1, IECC 2018. 2. Provide instructions for setting the operating parameters of the new smart exhaust fan to provide whole-house ventilation. Reference: Section R403.6, IECC 2018. |
02/17/2022 | ROBERT SHERRY | WATER | REVIEW | Passed | |
02/18/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/18/2022 | JVINCEN1 | FIRE | REVIEW | Approved | |
03/07/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. Provide complete up to date electrical plans that correlate with the Mechanical and Plumbing plans installation. Correlate equipment specification requirements for voltage, amperage, phase, and maintenance receptacles (where required per NEC) between Electrical and Mechanical/Plumbing plans. Include electrical load calculations where load increases from the original installation. 2. All Electrical plans are required to be sealed by a Registrant registered in the State of Arizona. Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |
03/08/2022 | IMONSHI1 | ZONING | REVIEW | Approved | |
03/08/2022 | IMONSHI1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed |