Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM00952
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/16/2022 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 02/17/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 02/17/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Demonstrate energy code compliance of the replacement windows with the current code. Reference: Section R503.1.1.1, International Energy Conservation Code 2018. 2. Provide instructions for setting the operating parameters of the new smart exhaust fan to provide whole-house ventilation. Reference: Section M1505.4.1, IRC 2018. |
| 02/17/2022 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 02/18/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/18/2022 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 03/07/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. Provide complete up to date electrical plans that correlate with the Mechanical and Plumbing plans installation. Correlate equipment specification requirements for voltage, amperage, phase, and maintenance receptacles (where required per NEC) between Electrical and Mechanical/Plumbing plans. Include electrical load calculations where load increases from the original installations. 2. There is no record of previous Electrical permitted upgrades for Building # 2. 3. All Electrical plans are required to be sealed by a Registrant registered in the State of Arizona. Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |
| 03/08/2022 | IMONSHI1 | ZONING | REVIEW | Approved | |
| 03/08/2022 | IMONSHI1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed |