Permit Number: T22CM00951
Parcel: 13622025A

Address:
7626 E 38TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM00951
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2022 SBLOOD1 ENGINEERING REVIEW Passed
02/22/2022 PAUL CAMARENA ZONING REVIEW Approved
02/25/2022 AWARNER1 NPPO REVIEW Passed
03/02/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00951

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. 2018 IRC Section R106.1.1. Revise construction documents by removing all references to "2019" applicable codes on sheets 1, 2, 4, 5 and 7.
2. 2018 IRC Section R106.1.1. Revise site plan drawing with locations, sizes, and meters of building utility lines for gas, water, electric and sewer or septic lines from property line to building.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
No Mechanical


ELECTRICAL REVIEW COMMENTS
Denied
1. 2018 IRC Section E3901.7 and E3902.3. Revise drawings with not less than one outdoor GFCI receptacle outlet that is readily accessible from grade level at the front and back of each dwelling unit.


PLUMBING REVIEW COMMENTS:
Conditionally Approved
No Plumbing