Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM00950
Parcel: 115052410

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00950
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/21/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/18/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved Please address the electrical plan review comments and provide a written response.

1. It was requested to update the electrical plans per the previous electrical plan review comments. The exhaust fans, wiring, and controls could not be located on the electrical plans submitted and stamped 3-9-2018. Please update the plans and registrant stamp.

Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements