| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/21/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 04/18/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Please address the electrical plan review comments and provide a written response. 1. It was requested to update the electrical plans per the previous electrical plan review comments. The exhaust fans, wiring, and controls could not be located on the electrical plans submitted and stamped 3-9-2018. Please update the plans and registrant stamp. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |