Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM00949
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/09/2022 | GPENNIN1 | ZONING | REVIEW | Approved | |
| 02/16/2022 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 02/25/2022 | AWARNER1 | NPPO | REVIEW | Passed | |
| 03/02/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM00949 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Denied 1. 2018 IRC Section E3902.16 and E3902.17. Revise electrical drawing with arc-fault circuit-interrupter protection for branch circuits 120-volt, single-phase, 15- and 20-ampere outlets installed in kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreations rooms, closets, hallways, laundry areas and similar rooms or areas. 2. 2018 IRC Section E4002.14. Tamper resistant receptacles are required in most locations. 3. 2018 IRC Section E3401.2. Electrical systems, equipment or components not specifically covered in IRC chapters 34 through 43 shall comply with the provisions of NFPA 70 including overhead feeder installations. Provide additional information on weather proof wiring, weather heads and roof clearances on riser diagram on sheet 5 (NEC Article 225). PLUMBING REVIEW COMMENTS: Approved |