Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Previous review comment #1 not completely addressed. Section 403.5.1 requires the timer to be equipped with minimum 6 hours of stand-by power. Please verify. Also provide permanent signage at the timer as required per OLC. See section 403.5.

2. Per comment #3 (Parcel 1 and 2). Please indicate Parcel ID numbers to verify actual size per Pima County Assessor Data.

3. Per previous review comment #4. Verify compliance with OLC section102.4.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code (OLC).
06/20/2022 STEVE SHIELDS ZONING REVIEW Reqs Change Zoning cannot approve this building permit until the associated Development Package (DP) is approved and the building plans are reviewed against the DP for compliance.
06/20/2022 SSHIELD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.