Permit Number: T22CM00948
Parcel: 132190080

Address:
2075 E BENSON HY

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM00948
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Verify curfew time switching controls for unshielded luminaires comply with OLC section 403.5.1, (Stand by Power).

2. Insert a note in the lighting plan stating whether or not a special inspection is required per OLC section 104.2.2, and comply with section 106.2.1.

3. Why is the parcel size shown in the lumen calculations divided into size 1 and size 2?

4. Provide compliance with section 102.4.2 OLC. Show all exterior luminaires on the site plan, existing and new and correlate with the quantities shown in the lumen calculations. If applicable.



Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code (OLC).
03/09/2022 LSHAMIS1 ZONING REVIEW Reqs Change Zoning cannot approve this building permit until the associated Development Package (DP) is approved and the building plans are reviewed against the DP for compliance.
03/18/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
03/18/2022 VVERA1 OUT TO CUSTOMER Completed