Permit Number: T22CM00829
Parcel: 10504136B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00829
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00829

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. There is a difference between exit signage and means of egress illumination. No egress illumination is being provided on the RCP. Provide egress illuminations in accordance with Section 1008.


MECHANICAL REVIEW COMMENTS:
Denied
1. Comment letter for KC mechanical not provided. Provide comment response letter.
2. Please provide a COMcheck that indicates compliance for new mechanical system and scan that data onto one of the mechanical sheets. This provides evidence the mechanical system is in compliance.
3. Some equipment seems to be missing from the floor plan in addition to the equipment schedule. Provide clarification.


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Approved