Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM00829
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/07/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM00829 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Denied 1. There is a difference between exit signage and means of egress illumination. No egress illumination is being provided on the RCP. Provide egress illuminations in accordance with Section 1008. MECHANICAL REVIEW COMMENTS: Denied 1. Comment letter for KC mechanical not provided. Provide comment response letter. 2. Please provide a COMcheck that indicates compliance for new mechanical system and scan that data onto one of the mechanical sheets. This provides evidence the mechanical system is in compliance. 3. Some equipment seems to be missing from the floor plan in addition to the equipment schedule. Provide clarification. ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: Approved If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |