Permit Number: T22CM00788
Parcel: 127034330

Address:
5702 E 3RD ST

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM00788
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2022 ARUIZ1 OIP REVIEW Reqs Change FROM:
PDSD Residential Review Section

PROJECT: T22CM00788
Roof top Solar Panels (1st Review)


TRANSMITTAL DATE: March 11, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


• COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments

COMMENT: This plan set is not compliant with the Fire code, demonstration compliance to 2018 International Fire Code 1204.2.1.1. If the slope of the building is greater than 2:12 then compliance must be shown on the plans. Show a 36” wide access pathway from the eave to the ridge on both sides of the building.

• COMMENT: Residential will review the application on the next submittal

If you have any questions about this transmittal, Contact any time during the week by email Angie.Ruiz@Tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
03/11/2022 VVERA1 OUT TO CUSTOMER Completed