| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2022 | ARUIZ1 | OIP | REVIEW | Reqs Change | FROM: PDSD Residential Review Section PROJECT: T22CM00788 Roof top Solar Panels (1st Review) TRANSMITTAL DATE: March 11, 2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed. • COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments COMMENT: This plan set is not compliant with the Fire code, demonstration compliance to 2018 International Fire Code 1204.2.1.1. If the slope of the building is greater than 2:12 then compliance must be shown on the plans. Show a 36” wide access pathway from the eave to the ridge on both sides of the building. • COMMENT: Residential will review the application on the next submittal If you have any questions about this transmittal, Contact any time during the week by email Angie.Ruiz@Tucsonaz.gov |