Permit Number: T22CM00776
Parcel: 133322180

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM00776
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2022 SBLOOD1 ENGINEERING REVIEW Passed
02/17/2022 IMONSHI1 ZONING REVIEW Reqs Change FROM: Iman Monshizadeh

PDSD Zoning Review Section

PROJECT: T22CM00776 – Bedroom Addition

Plot Plan Review (1st Review)

8841 E Vicksburg St / R-1 Zone

TRANSMITTAL DATE: 02/16/2022



Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.



1.COMMENT: As per UDC 4.9.7.B.7: “For any new single-family dwelling in the R-1 zone with five bedrooms , three parking spaces are required”

Bedroom count including the den and office (which count as a bedrooms) totals 5 bedrooms.

On the next submittal show that there is enough space in the rear or side of the property for 3 parking spaces 8.5’ W x 18’L. As long as space is shown we will accept, no changes have to be made on site.



For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp
02/17/2022 IMONSHI1 NPPO REVIEW Passed
02/23/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00776

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Denied
1. 2018 IRC Section P3105. Revise plumbing drawing with a vent for each fixture trap.