Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM00759
Parcel: 116162790

Address:
921 N MAIN AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00759
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00759

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Resolved. 2018 IRC Section R106.1.1. Revise construction documents with references to 2018 International Residential Code.
2. Unresolved. 2018 IRC Section R106.1.1. Revise site plan drawing with locations, sizes, and meters of building utility lines for gas, water, electric and sewer or septic lines from property line to building.
3. Resolved. 2018 IRC Section R303.10 Revise drawings with required heating in new addition.
4. Unresolved. 2018 IRC Section 314.2, R314.3 and R314.4. Revise electrical drawing with smoke detectors in bedrooms and outside of bedroom areas and to be interconnected in such a manner that the actuation of one alarm will activate all of the alarms in the individual dwelling unit.
5. Unresolved. 2018 IRC Section 315.2 and R315.3. Revise drawings with location of carbon monoxide alarm outside of the bedroom(s) when the dwelling unit includes a fuel-fired appliance and/or has an attached garage.
6. Unresolved. 2018 IRC Section R506.2.3. Revise drawings with 6-mil polyethylene or approved vapor retarder with joints lapped not less than 6 inches placed between the concrete slab and the base course or prepared subgrade.
7. Unresolved - 2018 IRC Section N1102.2.2. Revise drawings with sufficient space for the required insulation of R-38 in between rafters (2x12 rafters required). 2018 IRC Table R802.4.1.(2). Revise drawings with lumber species and grade used in designing rafter spans (2x6@24o.c. will not span 15').


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Conditionally Approved
No Plumbing


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov