Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00759

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied - Changes not addressed on resubmittal
1. 2018 IRC Section R106.1.1. Revise construction documents with references to 2018 International Residential Code.
2. 2018 IRC Section R106.1.1. Revise site plan drawing with locations, sizes, and meters of building utility lines for gas, water, electric and sewer or septic lines from property line to building.
3. 2018 IRC Section R303.10 Revise drawings with required heating in new addition.
4. 2018 IRC Section 314.2, R314.3 and R314.4. Revise electrical drawing with smoke detectors in bedrooms and outside of bedroom areas and to be interconnected in such a manner that the actuation of one alarm will activate all of the alarms in the individual dwelling unit.
5. 2018 IRC Section 315.2 and R315.3. Revise drawings with location of carbon monoxide alarm outside of the bedroom (s) when the dwelling unit includes a fuel-fired appliance and/or has an attached garage.
6. 2018 IRC Section R506.2.3. Revise drawings with 6-mil polyethylene or approved vapor retarder with joints lapped not less than 6 inches placed between the concrete slab and the base course or prepared subgrade.
7. 2018 IRC Table R802.4.1.(2). Revise drawings with lumber species and grade used in designing rafter spans (2x6@24o.c. will not span 15').


MECHANICAL REVIEW COMMENTS:
Denied - Changes not addressed on resubmittal

1. 2018 IRC Section M1201.1 and M1301.1. Provide mechanical drawings for review before installation.


ELECTRICAL REVIEW COMMENTS
Denied - Changes not addressed on resubmittal

1. 2018 IRC Section E3901.7 and E3902.3. Revise drawings with not less than one outdoor GFCI receptacle outlet that is readily accessible from grade level at the front and back of each dwelling unit.


PLUMBING REVIEW COMMENTS:
Denied - Changes not addressed on resubmittal

1. 2018 IRC Section P2601 through P2609. Provide plumbing drawings for review before installation.
03/14/2022 STEVE SHIELDS ZONING REVIEW Approved