Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM00756
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/16/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM00756 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Conditionally Approved. 1. The service corridor doors do not swing in the path of egress. Provide a corrected door swing. MECHANICAL REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: Denied THIRD REVIEW: 1 THRU 11 OK 12).OK 13). OK 14). OK 15). ok 16). SAME-LABEL THE RESTROOMS THAT HAVE MULTIPLE TOILETS ON PLAN PAGE A1 MENS & WOMENS. - IPC 403.2 (Label 1 mens) (Label 1 women's) If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
05/19/2022 | JPEELDA1 | FIRE | REVIEW | Approved |