04/22/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00756

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Provide a separate egress plan. The egress plan should show the location of furniture and equipment with the travels distances shown clearly. The travel distances are not provided on the egress plan. Provide all travel distances iand a separate and distinct egress plan.


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
SECOND REVIEW:
1 THRU 11 OK
12). SAME-. Add fixture spacing measurements details for dual lavs to plan pg. A1.2. -IPC 405.3.1 (SIDE WALL TO FIXTURE CENTER & FIXTURE TO FIXTURE CENTER MEASUMENTS)
13). OK
14). SAME- PLAN PAGE A1.2 STATES PREFAB SHOWER UNIT, ADD MANUFACTURE NAME & MODEL TO P7 FIXTURE SCHEDULE. -IPC 301.3
15). ok
16). LABEL THE RESTROOMS THAT HAVE MULTIPLE TOILETS ON PLAN PAGE A1 MENS & WOMENS. - IPC 403.2


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
05/09/2022 JPEELDA1 FIRE REVIEW Reqs Change Looking for the next review