Permit Number: T22CM00747
Parcel: 117024060

Address:
901 N PERRY AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00747
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/26/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T22CM00747
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet Zoning and other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

GENERAL COMMENTS:

1. Items built without permit may require alteration or improvement for code compliance with the 2018 IRC, R105. Show the as-built addition with necessary alterations for achieving code compliance for the north porch.

SECTIONS - DETAILS:

1. Limit cantilevered rafters (overhang) to 24”, or provide engineered design, R802.7.1.1.
2. Provide roof tie-down consistent with R804.3. Update detail 1 & 2 sheet S-1 with fastener sizes.

ELECTRICAL PLANS:

1. Show the mast height on the electrical riser diagram providing 8’ clearance above the Studio roof, E3604.2.1. Clarify the location of the property service meter after coordinating the utility plan with Tucson Electric Power.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
06/14/2022 STEVE SHIELDS ZONING REVIEW Approved