Permit Number: T22CM00730
Parcel: 14002010A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T22CM00730
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM00730
3950 E Irvington Rd – PAD-34
TEP Warehouse Addition (Revision #1 - 1st Review)

TRANSMITTAL: September 13, 2022

This site is located in the PAD-34

1. The canopy shown along the west side of the building does not match what is shown on DP21-0273. Unit the plans match Zoning cannot approve the plans.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
09/20/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00730

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved
Comment only: Fire pump ATS only needs to be sized to be equal or above the current carrying capacity of properly sized conductor feeders


PLUMBING REVIEW COMMENTS:
Denied
First Revised Plan Plumbing Review:
1). Plan Page P1.0 Floor Drain in Fire Pump Room needs to connect to the sanitary sewer. IPC 301.3 ( doesn't Meet Exception)
2). Fire Pump floor drain on P1.0 needs trap seal protection. -IPC 1002.4.1
3). P1.0 Fire pump room floor drain needs to be vented. -IPC 901.2.1
4). Is the added generator within the electrical plans natural gas or propane? if yes provide complete gas plans. -IFGC 106.3.1


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
09/26/2022 JPEELDA1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/26/2022 NGARCIA3 OUT TO CUSTOMER Completed