Permit Number: T22CM00730
Parcel: 14002010A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00730
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2022 DBENOIT1 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00730

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
Second Review:
1), Now that gutter sizes for roofs E & F have been added to the sizing table on plan 3A23.0 Gutters E & F are undersized. - IPC 1106.6
2-4 Ok


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
04/12/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM00730
3950 E Irvington Rd – PAD-34
TEP Warehouse Addition (2nd Review)

TRANSMITTAL: April 12, 2022

This site is located in the PAD-34

1. Zoning has reviewed the building plans for compliance with DP21-0273 but until the DP is approved Zoning cannot approve the building plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.