Permit Number: T22CM00730
Parcel: 14002010A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM00730
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2022 ROBERT SHERRY WATER REVIEW Completed
02/25/2022 JPEELDA1 FIRE REVIEW Approved
02/28/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00730

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Sheet 2g2.1: The occupant load calculations are not correct. The training room and the break room would be considered an assembly space. This may require additional exits. Provide corrected occupant load calculations in accordance with Table 1004.5.
2. The travel on the stairs must be included in the travel distance to the exit.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
1. Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
1). Add gutter sizes for Roofs E & F to calculation table on plan page 3A3.0
2). Show the lavatory center to side wall distance & the multiple lav center to separation distances to plan pages 1P1.0 & 2P2.1. -IPC 405.3.1
3). Service Sink is required update all affected pages. If existing show locations. - IPC 403.1
4). Sanitary Riser diagram #2 on P1.1 is illustrating incorrect direction of flow. -IPC 706.3
03/03/2022 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: PDSD Zoning Review

PROJECT:
T22CM00730
3950 E Irvington Rd – PAD-34
TEP Warehouse Addition (1st Review)

TRANSMITTAL: March 3, 2022

This site is located in the PAD-34

1. Zoning has reviewed the building plans for compliance with DP21-0273 but until the DP is approved Zoning cannot approve the building plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
03/03/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
03/18/2022 SBLOOD1 ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/18/2022 VVERA1 OUT TO CUSTOMER Completed