Permit Number: T22CM00724
Parcel: 11706067A

Address:
224 N 4TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM00724
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0; Floor Plan: Per the IBC Table 1006.2.1, a space with a B Occupancy Classification and less than 30 occupants is allowed a maximum common path of egress travel distance of 100'. The path from the sink (Keynote 15) in Wash Room 108 to the exit exceeds 100'. Please verify, and indicate the common path of egress travel distance on the plan.
2. Sheet A3.0; Reception Desk (8): Per the ICC/ANSI Section 904.3, sales and service counters require the counter to be a maximum of 36" in height above the finish floor. Section A indicates a 3'-6" counter height. Please verify.
02/08/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/08/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/08/2022 ROBERT SHERRY WATER REVIEW Completed
02/23/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Ref; Plan sheet E3.0

Is panel ‘A’ a 200 amp or 400 amp panel? See panel schedule for ‘A’. Please clarify.

What size OCPD is feeding panel ‘B’ ?

Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
03/02/2022 WBERGER1 ZONING REVIEW Approved
03/02/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/05/2022 JVINCEN1 FIRE REVIEW Approved
03/18/2022 SBLOOD1 ENGINEERING REVIEW Passed