Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM00720
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/01/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Show the location of the subpanels being replaced, and new locations for the new subpanels. Be advised of the locations not allowed per NEC 240.24D, 240.24E,408.16, 408.17 and clearances per NEC 110.26. Provide a symbol schedule to explain what the triangles represent at the panel schedules. Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/01/2022 | VVERA1 | OUT TO CUSTOMER | Completed |