Permit Number: T22CM00716
Parcel: 115072670

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00716
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. The IECC calculations for the lighting is in correct. Could not locate Table 505..5.2 in the 2018 IECC Code. Provide compliance with section 405, 2018 IECC.

2. Ref; 2012 Tucson/Pima County Outdoor Lighting Code (OLC). A. The Outdoor Lighting Code calculations is incorrect. Please use the correct Option per table 401.1. OLC, unless there are really LPS luminaires within this parcel. If there is, please show the quantity and location. B. Verify that the Parcel size is correct. The site sq. footage shown in the civil plan does not correlate with the acreage size shown in the lumen calculations.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code (OLC).
06/02/2022 WBERGER1 ZONING REVIEW Reqs Change RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Please resubmit updated drawings along with a detailed comment response letter, which states how all zoning review comments were addressed.

2. COMMENT: This comment was not addressed, as the previous lot coverage calculations are still on the revised plan set. Correct the allowed lot coverage calculation on C1.0. There is no lot coverage maximum for non-residential uses within the C-3 zone.
3. COMMENT: This comment was not addressed. Clarify whether the proposed use is Business Supply and Equipment Wholesaling (UDC 11.3.12.A), Commercial Storage (UDC 11.3.10.A), or General Merchandise Sale, excluding Large Retail Establishment (UDC 11.3.9.C). "Wholesale gem" is not a defined UDC land use class/type.
4. COMMENT: This comment was not addressed. Demonstrate compliance with all sections of UDC 3.3.3.H. Provide either form of documentation within 3.3.3.H.9 with the next submittal. Either submit a sworn affidavit that the use of the property will be in compliance with the section, or include the following in any lease/rental agreement for the property: "Tenant shall not cause or permit the Property to be used in any way which constitutes a violation of any law, ordinance or governmental regulation. Notwithstanding any contrary provision of this lease agreement, any occupancy or use of the premises in violation of this paragraph constitutes a material breach of this lease agreement entitling Lessor to involve all remedies provided hereunder including termination.