Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM00716
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/07/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/07/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | No mechanical work shown |
| 02/07/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 02/07/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/23/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1 . Ref; Plan Sheet E0.1. Indicate if the electrical service entrance/CT, meter, main service disconnect is new or existing. If new, show all conduit, conductor sizes and types in the line diagram including the service riser. Indicate the correct number and size of feeder conductors feeding the 400 amp 3-phase panel. The line diagram shows panel ‘B’ as a 1-phase panel and the panel schedule for ‘B’ indicates 3-phase. Please clarify. Indicate the available fault current at the electrical service (Per TEP) and the main disconnect fuse sizes and types. Balance the loads between phases in the load centers (panels) NEC 210.11B, 408B. Motor loads to be calculated at 125% not 112.5%, Nec 220.18A, 430.22. Provide more detail in the panel directories as to the identify the device(s) or motors, include evap coolers. NEC 408.4A. 2. Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting. 3. Provide compliance with the 2018 IECC for the lighting. Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
| 03/03/2022 | WBERGER1 | ENGINEERING | REVIEW | Passed | |
| 03/03/2022 | WBERGER1 | ZONING | REVIEW | Reqs Change | RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Please resubmit updated drawings along with a detailed comment response letter, which states how all zoning review comments were addressed. 1. COMMENT: As the existing building and patio footprint cross property lines, a lot combination shall occur before zoning can approve. Provide lot combination documentation with the next submittal. 2. COMMENT: Correct the allowed lot coverage calculation on C1.0. There is no lot coverage maximum for non-residential uses within the C-3 zone. 3. COMMENT: Clarify whether the proposed use is Business Supply and Equipment Wholesaling (UDC 11.3.12.A), Commercial Storage (UDC 11.3.10.A), or General Merchandise Sale, excluding Large Retail Establishment (UDC 11.3.9.C). 4. COMMENT: Demonstrate compliance with all sections of UDC 3.3.3.H. Additionally, provide either form of documentation within 3.3.3.H.9 with the next submittal. If you have any questions about this transmittal, contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov. |
| 03/03/2022 | WBERGER1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/05/2022 | JVINCEN1 | FIRE | REVIEW | Approved |