Permit Number: T22CM00716
Parcel: 115072670

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM00716
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/07/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed No mechanical work shown
02/07/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/07/2022 ROBERT SHERRY WATER REVIEW Completed
02/23/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 . Ref; Plan Sheet E0.1.

Indicate if the electrical service entrance/CT, meter, main service disconnect is new or existing. If new, show all conduit, conductor sizes and types in the line diagram including the service riser.

Indicate the correct number and size of feeder conductors feeding the 400 amp 3-phase panel.

The line diagram shows panel ‘B’ as a 1-phase panel and the panel schedule for ‘B’ indicates 3-phase. Please clarify.

Indicate the available fault current at the electrical service (Per TEP) and the main disconnect fuse sizes and types.

Balance the loads between phases in the load centers (panels) NEC 210.11B, 408B.

Motor loads to be calculated at 125% not 112.5%, Nec 220.18A, 430.22.

Provide more detail in the panel directories as to the identify the device(s) or motors, include evap coolers. NEC 408.4A.

2. Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting.

3. Provide compliance with the 2018 IECC for the lighting.

Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
03/03/2022 WBERGER1 ENGINEERING REVIEW Passed
03/03/2022 WBERGER1 ZONING REVIEW Reqs Change RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Please resubmit updated drawings along with a detailed comment response letter, which states how all zoning review comments were addressed.

1. COMMENT: As the existing building and patio footprint cross property lines, a lot combination shall occur before zoning can approve. Provide lot combination documentation with the next submittal.
2. COMMENT: Correct the allowed lot coverage calculation on C1.0. There is no lot coverage maximum for non-residential uses within the C-3 zone.
3. COMMENT: Clarify whether the proposed use is Business Supply and Equipment Wholesaling (UDC 11.3.12.A), Commercial Storage (UDC 11.3.10.A), or General Merchandise Sale, excluding Large Retail Establishment (UDC 11.3.9.C).
4. COMMENT: Demonstrate compliance with all sections of UDC 3.3.3.H. Additionally, provide either form of documentation within 3.3.3.H.9 with the next submittal.

If you have any questions about this transmittal, contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov.
03/03/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/05/2022 JVINCEN1 FIRE REVIEW Approved