Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T22CM00705
Parcel: 11202033F

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM00705
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2022 ROBERT SHERRY WATER REVIEW Completed
02/04/2022 JGARCIA1 ZONING REVIEW Passed
02/04/2022 JGARCIA1 ENGINEERING REVIEW Passed
02/04/2022 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/10/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/15/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the mechanical design as required to avoid using the corridors as return air ducts. Reference: Section 601.2, IMC 2018.
02/15/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide specifications and a water supply for the "water station" noted on sheet A101. The use of a point-of-use water dispenser in lieu of a drinking fountain requires the installation of a listed and labeled dispenser along with a permanently mounted disposable cup dispenser. The cup dispenser shall be located adjacent to the water dispenser with the dispensing end between 34" and 48" above the finished floor
2. Provide details showing how the proposed shower enclosure complies with the requirements of 421, IPC 2018.
02/16/2022 JVINCEN1 FIRE REVIEW Reqs Change Online the building shows that it is connected to 3940 without a parapet that might be a separation. If the buildings are not separate both shall have fire sprinklers installed. Show separation on drawings if one exists.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
02/28/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Ref; Plan sheet E2.1

Please address the branch circuits circuiting for the lighting for the new or replaced luminaires. If they are all utilizing existing circuits with no increased loads, please address this with a note.

2. Some of the rooms do not show the switched branch circuits wiring from the switch(s) to the luminaires single and dual switched. Please show this in the lighting plan.

Ref; Plan Sheet E1.1 and P2. The plumbing plans show an electric water heater being installed. Verify the power floor plan addresses this. If the water heater increases the load, please address this with a panel schedule showing load calculations.

Please show the exhaust fan in the utility room. See mechanical plan M1.

Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.