Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM00676
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/07/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Show that the gypsum board within 18" of the hood is covered with a "smooth, cleanable, nonabsorbent and noncombustible material", (e.g. stainless steel Reference: Section 507.2.6, IMC 2018. [Second comment: Show that the hood (not the exhaust duct) complies with Section 507.2.6, IMC 2018 for clearance from combustibles.] [Initial comment: Show that the hood installation complies with Section 507.2.6, IMC 2018 for clearances.] |
| 06/07/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/07/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. A symbol for an EWH is shown for the two lavatories but no instant hot water heater has been specified. Reference: Section 107.2.1, IBC 2018. [Second comment: Comment not resolved. The maximum distance from the hot water source to the hot water termination at a public lavatory is 24" for ½" pipe or 6" for ¾" pipe. See Table C404.5.1, IECC 2018.] [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.]. 2. The revised waste piping drawing shows a vent below grade for the grease interceptor. All vents (except for vents serving interceptors located outdoors) shall rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2018. [Second comment: See the grease interceptor requirements in the City of Tucson amendments to the 2018 IPC. See https://www.tucsonaz.gov/files/integrated-planning/2018_-_IPC_Amendments.PDF [Initial comment: Provide a grease interceptor to prevent the discharge of fats, oil, and grease into the public sewer. The restroom fixtures shall not discharge through the grease interceptor. Reference: Sections 1003.1 and 1003.3.1, IPC 2018 as amended by the City of Tucson.] |