Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T22CM00676
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/21/2022 | WBERGER1 | ZONING | REVIEW | Approved | |
| 04/21/2022 | WBERGER1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/01/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/04/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Show that the hood (not the exhaust duct) complies with Section 507.2.6, IMC 2018 for clearance from combustibles. [Initial comment: Show that the hood installation complies with Section 507.2.6, IMC 2018 for clearances.] |
| 05/04/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not resolved. The maximum distance from the hot water source to the hot water termination at a public lavatory is 24" for ½" pipe or 6" for ¾" pipe. See Table C404.5.1, IECC 2018. [initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.] 2. See the grease interceptor requirements in the City of Tucson amendments to the 2018 IPC. See https://www.tucsonaz.gov/files/integrated-planning/2018_-_IPC_Amendments.PDF [initial comment: Provide a grease interceptor to prevent the discharge of fats, oil, and grease into the public sewer. The restroom fixtures shall not discharge through the grease interceptor. Reference: Sections 1003.1 and 1003.3.1, IPC 2018 as amended by the City of Tucson.] 3. Sheets M1, M3, M4, and M8 all provide references to an evaporative cooler to provide make up air. The evaporative cooler section in the CaptiveAire make up air unit does not comply with the water recirculation requirements of the State of Arizona but the Champion evaporative cooler, specified on sheet M1does meet the State requirements. [initial comment: Show how water and drain will be provided for the proposed evaporative cooler. Reference: Section 107.2.1, IBC 2018.] |
| 05/04/2022 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Clarify your response. No 1-1/4" water meters are used by Tucson Water; do you mean a 1-1/2" is installed? Does the water meter serve just this address or does it serve several addresses at Gee Plaza? Provide the total water demand served by this water meter. [initial comment: Provide the size of the water meter serving this address, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1 and 107.2.6, IBC 2018.] |
| 05/16/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |