Permit Number: T22CM00676
Parcel: 11206009B

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T22CM00676
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2022 WBERGER1 ZONING REVIEW Approved
04/21/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/01/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/04/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show that the hood (not the exhaust duct) complies with Section 507.2.6, IMC 2018 for clearance from combustibles. [Initial comment: Show that the hood installation complies with Section 507.2.6, IMC 2018 for clearances.]
05/04/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not resolved. The maximum distance from the hot water source to the hot water termination at a public lavatory is 24" for ½" pipe or 6" for ¾" pipe. See Table C404.5.1, IECC 2018. [initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.]
2. See the grease interceptor requirements in the City of Tucson amendments to the 2018 IPC. See https://www.tucsonaz.gov/files/integrated-planning/2018_-_IPC_Amendments.PDF [initial comment: Provide a grease interceptor to prevent the discharge of fats, oil, and grease into the public sewer. The restroom fixtures shall not discharge through the grease interceptor. Reference: Sections 1003.1 and 1003.3.1, IPC 2018 as amended by the City of Tucson.]
3. Sheets M1, M3, M4, and M8 all provide references to an evaporative cooler to provide make up air. The evaporative cooler section in the CaptiveAire make up air unit does not comply with the water recirculation requirements of the State of Arizona but the Champion evaporative cooler, specified on sheet M1does meet the State requirements. [initial comment: Show how water and drain will be provided for the proposed evaporative cooler. Reference: Section 107.2.1, IBC 2018.]
05/04/2022 ROBERT SHERRY WATER REVIEW Reqs Change Clarify your response. No 1-1/4" water meters are used by Tucson Water; do you mean a 1-1/2" is installed? Does the water meter serve just this address or does it serve several addresses at Gee Plaza? Provide the total water demand served by this water meter. [initial comment: Provide the size of the water meter serving this address, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1 and 107.2.6, IBC 2018.]
05/16/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved