Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM00676
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/03/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Faucets serving lavatories in all buildings other than R3 occupancies, individual units in R2 occupancies, or International Residential Code structures shall be automatic faucets dispensing a maximum of 0.25 gallons per cycle. The cycle time shall not be less than ten-seconds for accessibility. Reference: Section 419.6, IPC 2018 as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. 3. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1, 504, 606.1, 607.2, and 607.3, IPC 2018. 4. Appliances (e.g. beverage dispensers, ice makers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2018 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2018. 5. Provide indirect waste piping for the 3-compartment sink. Reference: Section 802.1, IPC 2018. 6. Provide a grease interceptor to prevent the discharge of fats, oil, and grease into the public sewer. The restroom fixtures shall not discharge through the grease interceptor. Reference: Sections 1003.1 and 1003.3.1, IPC 2018 as amended by the City of Tucson. 7. Show how water and drain will be provided for the proposed evaporative cooler. Reference: Section 107.2.1, IBC 2018. |
| 02/03/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Relocate the supply air diffuser for MUA-1 at least ten feet from the face of the hood or provide perforated diffusers to avoid disrupting the airflow into the hood. (Note: The CaptiveAire submittal drawings on sheets M5 and M6 show a supply air plenum attached to the Type I hood. Is this plenum to be installed?) Reference: Section 304.1, IMC 2018. 2. Show the size, routing, and termination of the condensate drains for the two roof-mounted heat pumps. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson. 3. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018. 4. Ventilation for restrooms in public spaces requires a minimum of 50 CFM of mechanical exhaust per water closet or urinal if the exhaust is continuous and 70 CFM if the exhaust is intermittent. Reference: footnote e, Table 403.3.1.1, IMC 2018. 5. Show that the hood installation complies with Section 507.2.6, IMC 2018 for clearances. |
| 02/03/2022 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size of the water meter serving this address, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1 and 107.2.6, IBC 2018. |
| 02/10/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A001; Code Analysis: The Occupancy Type is A-2 (restaurant). Per the IBC Section 303.1.1, a tenant space used for assembly purposes with an occupant load of less than 50 persons shall be classified as a Group B Occupancy. Please add this verbiage to the Code Analysis. 2. Sheet A001; Code Analysis (Occupant Load): Per the IBC Table 1004.5, the Occupant Load Factor for Common Kitchens is 200. Please revise the Code Analysis and the Occupant Load as required. 3. Sheet A001; Code Analysis (Plumbing Fixtures): Please indicate Male and Female on the Total Required Plumbing Fixtures and the Total Provided Plumbing Fixtures. Include Lavatories Required and Lavatories Provided per the IBC Table 2902.1 for a Group B Occupancy Classification. 4. Sheet A201; Proposed Floor Plan: The Women's Restroom (106) is an existing restroom, so it may remain as is. The Men's Restroom (105) is a new restroom and therefore is required to be accessible. The 5'-0" clear dimension indicated on the plan does not meet the requirements of the 2009 ICC/ANSI Figure 604.3. Please provide an enlarged plan of the new restroom following the ICC/ANSI Section 604. 5. Sheet A201; Proposed Floor Plan: Per the IBC Section 1109.11, seating at tables and counters in accessible spaces must provide at least 5% accessible seating/standing locations. It appears there are 32 seats in the restaurant. This would require two accessible seating locations. Please indicate a second accessible seat on the plan. 6. Sheet A201; Proposed Floor Plan: Please indicate Wall Types on the plan for all new interior walls (no Wall Type "B" was located). 7. Sheet A901; Wall Type "A": Please indicate the wall stud size and spacing on this detail, or reference the Schedule in Detail 09. 8. Sheet A931; Restroom Mounting Heights: Please indicate a veritical grab bar on the Water Closet Side Wall using Figure 604.5.1 of the 2009 ICC/ANSI. 9. General: Please provide written responses to all review comments. |
| 02/22/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide compliance with the 2018 IECC for the lighting . Ref' 2018 IECC section 405. |
| 03/01/2022 | WBERGER1 | ENGINEERING | REVIEW | Passed | |
| 03/01/2022 | WBERGER1 | ZONING | REVIEW | Reqs Change | RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Please resubmit updated drawings along with a detailed comment response letter, which states how all zoning review comments were addressed. 1. COMMENT: As you are proposing an expansion of a Food Service use, demonstrate that 50% or more of all uses within the existing shopping center are not Food Service and Alcoholic Beverage Service uses to comply with parking standards. If more than 50% of all shopping center uses are Food Service and Alcoholic Beverage Service, a Development Package is required. If you have any questions about this transmittal, contact Wyatt Berger at 520-837-4951 or at Wyatt.Berger@tucsonaz.gov. |
| 03/05/2022 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 03/14/2022 | ARUIZ1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |