Permit Number: T22CM00671
Parcel: 115010110

Address:
2125 N 1ST AV

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM00671
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2022 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T22CM00671
Rooftop Solar Panels (1st Review)
2125 N 1ST AV

TRANSMITTAL DATE: ?March ?8, ?2022



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve it at this time. Please address the following comments

COMMENT: After comparing the aerials to the plot plan it has come to my attention that there is a possible non-permitted detached structure on the south portion of the property roof #3. After researching PRO there were no records for the detached structure that could be verified or found. If no permits are available relocate the solar panel away from the detached structure or a permit must be obtained for the detached structure.


COMMENT: Since the panels are going to be placed on two separate structures and one service shall continue to serve both structures, it is essential that all equipment and systems can be easily isolated at each building. Demonstrate how the equipment is going to be isolated by each structure.



COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Paul Camarena any time during the week by phone (520)837-4986 or email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
03/08/2022 NGARCIA3 OUT TO CUSTOMER Completed