Permit Number: T22CM00668
Parcel: 140180780

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM00668
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2022 SBLOOD1 ENGINEERING REVIEW Passed
02/10/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T22CM00668

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. Place the reference on the plans.

Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits

STRUCTURAL PLAN:

Show the proposed structure dimensions.

Show rafters sized with sufficient space for providing minimum required ceiling insulation, R301.1.

SECTIONS - DETAILS:

An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF.

Show a complete cross-section detail of the foundation #2 on sheet 2 with minimum #4 rebar reinforcement rather than pre-constructed, R106.1.1. Also, show the beam anchored to the foundation with minimum 7” embedment of the anchor bolts.

Show a door landing with step dimensions.

MECHANICAL PLANS:

Provide equipment details (heating/cooling device) showing code compliant components, locations and sizes.

ELECTRICAL PLANS:

Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16.

INTERNATIONAL ENERGY CONSERVATION CODE:

Provide insulation details minimum (R-13 walls and R-30 ceiling) showing code compliant placement of materials and ratings, N1101. Windows require a solar heat gain of 0.25 or better.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
02/11/2022 AWARNER1 NPPO REVIEW Passed
02/28/2022 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T22CM00668
Residential Addition February 28, 2022

The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed.

1. . Please resubmit the plans conforming to the requirements of the residential plot plan found at the following link: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf a. A full site plan with all setbacks, lot coverage calculations and other plot plan standards is required.

The applicant may use one of the pages of the following template as a base for the site plan. Ensure all required site plan requirements are provided: https://www.tucsonaz.gov/files/pdsd/forms/Mobile_Homes_Plot_Plans.pdf
To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp. If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov