Permit Number: T22CM00666
Parcel: 10408052D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00666
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM00666
451 W Auto Mall Dr – C-3
Storage Container Addition (2nd Review)

TRANSMITTAL: March 23, 2022

This site is located in the C-3 zone (UDC 4.7.22). Medical Service: Outpatient, limited to blood donor centers is a permitted use in this zone (Table 4.8-4) as a S = Permitted as Special Exception Use [1] Mayor and Council Special Exception Procedure, Section 3.4.4

1. This comment has not been addressed. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plans and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type “Site Review”.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
03/23/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00666


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Previous comment #2: While it's understood that exit 3 is not a required exit and only the occupants of the storage area would use that exit; all exits provided must be code compliant. Additionally, Sheet A001 clearly indicates the travel distance for individuals off the donor floor to exit 3 and is indicated to be used by those occupants. Provide updated floor plans that do not show exiting through the intervening storage space.
2. The north wall is within 10'-15' of the property line and will require a fire resistance rating of 1 hour. Provide an exterior wall assembly that meets the fire resistance rating in accordance with Table 602.
3. The north wall is within 10'-15' of the property line. The maximum amount exterior wall openings is 45%. Provide evidence of compliance with this requirement in accordance with Table 705.8.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
2. E101: RTU#1 needs to upsize conductor feed to #6 AWG as FLA is greater than 40 amps.
EOR response: BSC Response: Per Specification Section 26-0519 – Low Voltage Electrical Power Conductors and Cables, insulation types TW and UF are not called out to be used.
Reviewer: It is not the conductor, it is the lug/termination rating per NEC 110.14(C) which requires you to also use the 60 degree column for temperature/conductor application. If the lugs/terminations are known to be 75 degree rated, you do not have to upsize.


PLUMBING REVIEW COMMENTS:
Denied
Second Review:
1). SAME-Plan Page A343 shows roof drain detail, Plan page A141 needs to show roof drain locations. Pages need to correlate. IPC A106.3.1 **Per ONYX response building only has gutter & downspouts**- Remove roof drain detail if not used -IPC A106.3.1
2). OK -Plumbing pages need to illustrate above ground roof drain piping with sizing & GPM loads. -IPC 1106.2, A106.3.1 **DOWNSPOUTS**
3). SAME-Plan page A343 shows overflow scupper with downspout detail, plan page A141 needs to show overflow locations. plan pages need to correlate.**Per ONYX response building only has gutter & downspouts** -IPC A106.3.1 Remove scupper detail
4). SAME- Plan page A343 overflow scupper detail needs to include sizes & calculations. -IPC 1106.5, 1108.3-Remove scupper detail if not used
5). SAME-Plan page P110 & P111 shows an Overflow downspout detail connecting below grade, the secondary roof overflow drain needs to discharge above grade -IPC 1108.2.**Per ONYX response building only has gutter & downspouts** Remove underground storm continuation P110 & Downspout detail P111 if not used
6). SAME-Restroom #135 on plan page A153 toilet side wall to center measurement needs to comply with -IPC 405.3.1
7). SAME-Plan Page A153 needs to include lavatory side wall & center to center clearance measurements. -IPC 405.3.1
8). OK
9). Add gutter detail & sizing calculations to plan page P111 -IPC 1106.6


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
04/05/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change See zoning comments

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
04/08/2022 DBENOIT1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/08/2022 DBENOIT1 APPROVAL SHELF Completed
04/08/2022 DBENOIT1 OUT TO CUSTOMER Completed
04/08/2022 DBENOIT1 REJECT SHELF Completed