Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T22CM00654
Parcel: 99999999A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00654
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2022 DBENOIT1 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM00654


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approval/subject to field inspection


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Conditionally Approved
Second Plumbing Review:
Per response narrative & Fee schedule the Is a Tucson Utility owned Pump station & doesn't require Plumbing Approval


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov