Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM00654
Parcel: 99999999A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00654
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00654


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. The Seismic Parameters shown on Soil Report, Control Building and Proposed Steel Tank Calculations submitted does not match. Verify and make revisions as needed.
2. The Masonry Slender Wall calculations on page 6 for control building references IBC 2009. Revise calculations and resubmit.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approval/subject to field inspection


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Conditionally Approved
Second Plumbing Review:
Per response narrative & Fee schedule the Is a Tucson Utility owned Pump station & doesn't require Plumbing Approval


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov