Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM00650
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/09/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/22/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Ref; Plan sheet PV2.7 1 . Provide detailed information including specifications for the 2 new EV chargers, wiring methods. 2. Verify that the exterior luminaires installed under the canopies have full cut off shielding and lamp color temperature output temperature not exceeding 3500K sec 402.1 2012 Outdoor Lighting Code. Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
| 03/03/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 03/18/2022 | SBLOOD1 | ENGINEERING | REVIEW | Approved |