Permit Number: T22CM00627
Parcel: 13339283A

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T22CM00627
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2022 VFLORES1 COMMUNICATIONS REVIEW Reqs Change Revise form with corrected power figures and resubmit on website as an existing application. No comment response needed. Any questions contact IT_NS_CommEngineering@tucsonaz.gov
02/02/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/03/2022 JVINCEN1 FIRE REVIEW Approved
02/07/2022 SBLOOD1 ENGINEERING REVIEW Passed
02/15/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Ref; Plan Sheet E3.

1 . Provide a complete electrical line diagram and show all conductors, conduit sizes and types for the electrical service riser and if underground fed, the secondary conductor, conduit sizes and types.

2. What does "SBTC" mean for the grounding electrodes. Indicate this on the plan.

Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
02/28/2022 PETER MCLAUGHLIN ZONING REVIEW Completed
02/28/2022 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/08/2022 NGARCIA3 OUT TO CUSTOMER Completed