Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T22CM00627
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/28/2022 | VFLORES1 | COMMUNICATIONS | REVIEW | Reqs Change | Revise form with corrected power figures and resubmit on website as an existing application. No comment response needed. Any questions contact IT_NS_CommEngineering@tucsonaz.gov |
| 02/02/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/03/2022 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 02/07/2022 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 02/15/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Ref; Plan Sheet E3. 1 . Provide a complete electrical line diagram and show all conductors, conduit sizes and types for the electrical service riser and if underground fed, the secondary conductor, conduit sizes and types. 2. What does "SBTC" mean for the grounding electrodes. Indicate this on the plan. Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
| 02/28/2022 | PETER MCLAUGHLIN | ZONING | REVIEW | Completed | |
| 02/28/2022 | PETER MCLAUGHLIN | PLANNING-CITY HALL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/08/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |