Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM00618
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/23/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The specified water heater does not provide tempered water using an approved device conforming to ASSE 1070. Consult the manufacturer's technical literature to see how this can be accomplished. [Initial comment: Provide tempered water for the restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.] |
| 03/23/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 04/05/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. Please provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting. 2. Where is panel ‘A’ located? 3. Indicate the Available fault current at the electrical service and indicate the main service disconnect fuse sizes and types. 4. Verify correct OCPD rating and conductor sizes for the Insta Hot water heater. As the information is not available as stated in the electrical plan notes. Revise the load calculations if necessary. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |