Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM00618
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/01/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide tempered water for the restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018. |
| 02/01/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide a minimum exhaust flow rate of 50 CFM if the exhaust is continuous, 70 CFM if the exhaust is intermittent in the restroom. Reference: Section 403.3.1.1 and Table 403.3.1.1, IMC 2018. |
| 02/01/2022 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 02/09/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/16/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1 .Provide complete electrical plans. Show branch circuit and panel designations for all electrical devices, fans, lighting, receptacles, insta -hot water heater. 2. Provide a complete panel schedule that correlates with comment #1. Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
| 03/02/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 03/02/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/03/2022 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 03/17/2022 | SBLOOD1 | ENGINEERING | REVIEW | Passed |