Permit Number: T22CM00610
Parcel: 136261290

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00610
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/29/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/11/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The listing data for the proposed hood calls for greater exhaust and supply air flow rates than provided by the proposed exhaust fan and make up air unit. Reference: Section 304.1, IMC 2018. [Initial comment: Provide mechanical specifications for the proposed Type I hood. Include all operating requirements and the weight for the hood. Reference: Section 107.2.1, IBC 2018.]
04/11/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed